Dear all equest users,

This is my first trial in equest. I am now simulating a 4 pipe system
with chillers for cooling and air source heat pump for heating.

In wizard mode, only boiler can be selected for the hot water loop. How
can I change boiler to air source heat pump in detail mode?

Thank you .

Regards,

Daniel C Y Wong

Wong, Cheuk Yiu Daniel's picture
Joined: 2011-09-30
Reputation: 0

An air source heat pump attached to a water loop can either be modelled as a heat pump chiller attached to a two-pipe water loop, or you can use an electric boiler with an EIR at the heat pump's EIR. This doesn't capture the part load performance or the dependence on outdoor air temperatures; to capture this you will need to create hourly reports of the boiler demand, correlate these with the outdoor air temperature, and use the performance curves to calculate the actual energy usage of the boiler/heat pump.

All the best,
Dan

?
Daniel Knapp, PhD, LEED? AP O+M