HVAC Load Sizing Equations and conversions
Airside Load Equations:
For H listed in BTU/Hr
H
sensible
= 1.085*CFM*ΔT
H
Latent
= 0.68*CFMH
Total
*ΔW
LB
H
latent
= 4840*CFM*ΔW
Grains/LB
H
Total
= H
Sensible
+ H
Latent
H
Total
= 4.5*CFM*Δh
Enthalpy
SHR
= H
sensible
/H
Total
Water/Hydronic Load Equations:
MBH
= .5*GPM*ΔT
GPM
Evaporator
= 24*TONS/ΔT
GPM
Evaporator
= 30*TONS/ΔT
Where:
Δ = Delta
CFM = Cubic Feet Per Minute
GPM = Gallons Per Minute
Tons = Air conditioning load (=12,000 BTU/Hour)
SHR = Sensible Heat Ratio
*Note 1.085 is the Density specific Heat Product DSHP and subject to change by location!)