Hi,

Which output variable to look for finding the mass flow rate of PTAC supply
fan, if we autosize the supply air flow rate.

Thanks,

With regards,

Sachin Sharma

Sachin Sharma's picture
Offline
Joined: 2011-09-30
Reputation: 0

Dear Sachin,

Try these:

In the IDF:

Output:Variable, Name_dischargeNode, System Node Volume Flow Rate Standard
Density, Timestep;

In an RVI file:

Name_dischargeNode, System Node Volume Flow Rate Standard Density

In both cases "Name_dischargeNode" is the name that you are using for the
PTAC air outlet node.

James V. Dirkes II, P.E., BEMP , LEED AP

James V Dirkes II, PE's picture
Joined: 2011-10-02
Reputation: 203