Hi,
Which output variable to look for finding the mass flow rate of PTAC supply fan, if we autosize the supply air flow rate.
Thanks,
With regards,
Sachin Sharma
Dear Sachin,
Try these:
In the IDF:
Output:Variable, Name_dischargeNode, System Node Volume Flow Rate Standard Density, Timestep;
In an RVI file:
Name_dischargeNode, System Node Volume Flow Rate Standard Density
In both cases "Name_dischargeNode" is the name that you are using for the PTAC air outlet node.
James V. Dirkes II, P.E., BEMP , LEED AP
Dear Sachin,
Try these:
In the IDF:
Output:Variable, Name_dischargeNode, System Node Volume Flow Rate Standard
Density, Timestep;
In an RVI file:
Name_dischargeNode, System Node Volume Flow Rate Standard Density
In both cases "Name_dischargeNode" is the name that you are using for the
PTAC air outlet node.
James V. Dirkes II, P.E., BEMP , LEED AP