Dear all,

Is there any requirement for the COP of VRV systems in ASHRAE 90.1-2007?

I can't find that! If there is not, shall I assume that the baseline and
the proposed design for LEED purposes have the same COP?

Thanks!

Omar Katanani

Omar Katanani's picture
Offline
Joined: 2011-09-30
Reputation: 0

Refer to the attached Documents. For LEED you can use the actual COP of
the unit.

Rimes, Christie's picture
Offline
Joined: 2011-09-30
Reputation: 200

At the moment there is not. There will be a 90.1 minimum efficiency requirement in the near future however.

For LEED purposes you do not need to model a VRV system. You will model the appendix G Table G3.1.1A system type and the associated efficiency in 90.1 chapter 6.

Regards

Joe Fleming
E.I., LEED AP BD+C, BEMP

Fleming, Joe's picture
Offline
Joined: 2011-09-30
Reputation: 0

Ooops.. I forgot that!

Thanks for drawing my attention!

Best,

Omar Katanani

Omar Katanani's picture
Offline
Joined: 2011-09-30
Reputation: 0

Ashrae 90.1-2010 has min. requirements on this.