purchasing steam and chilled water from a provider

2 posts / 0 new
Last post

If a building is purchasing Steam and Chilled water from a service
provider and does not have boilers and chillers, then how can we input
this info into eQUEST and also the rate of the utility?

Your respond is much appreciated.

Regards,

Mo Vaziri

ON0F)'s picture
Offline
Joined: 2011-09-30
Reputation: 0

Using purchased steam and chilled water is easy.
First: In the water side HVAC tab create chilled water and hot water loops the same way you would if the chiller and boiler were being modeled and then add a "Chilled Water Meter" to your CHW loop and a "Steam Meter" to your HW loop.

[cid:743585121 at 15032010-1E26]

second: In the utility and economics tab create a "Chilled Water Meter" and "Steam Meter" with whatever rates you are using.
[cid:743585121 at 15032010-1E2D]

Hopefully this helps!

Heather Hardie-Hill

Heather.Hardie-Hill at CH2M.com's picture
Joined: 2011-09-30