Can anyone tell me how to enter the Supply fan power, in watts, and the brake horsepower of the baseline fans into my model? I calculated them according to ASHRAE 90.1, but can't figure out what to do with them now.

- Thank you,

Scott Tomlinson, PE, LEED-AP

Tomlinson, Scott's picture
Joined: 2011-09-30
Reputation: 0
Tomlinson, Scott's picture
Joined: 2011-09-30
Reputation: 0

Hi Scott,

In Baseline system, First of all you have to calculate Fan BHP as per G
3.12.9, and then with the help of calculated BHP you can derive the Fan
power (kW) as per section G3.1.29, then you can calculate the kW/CFM for
each system.

Now, you can put this kW/CFM multiplier in eQuest at Design kW/CFM in system
tab/Fan/Fan Flow parameters (Sample attached).

If kW/CFM tab is not activate on your system, go on side tab static (in WG)
and do default, then kW/CFM tab will be activate.

I hope this helps!

Thanks,

Ashu Gupta