In the BEPS report, the "Total Site Energy" is reported with a "MBTU"
value and a "kbtu/sqft-yr gross area" value. When the building area
(from the LV-B report) is multiplied by the "kbtu/sqft-yr gross area"
value, I would think it would equal the MBTU value on BEPS report, but
it does not. It actually equals about half that number.

Please let me know if anyone knows the reason for this.

Thanks,

David

David J. Thibodeau's picture
Joined: 2011-09-30
Reputation: 0

David,
The LV-B report includes unconditioned spaces and plenums, while the
"gross area" in the BEPS report defaults to the "net area", which only
includes conditioned zones.
Regards,

William Bishop, EIT, LEED(r) AP

Bishop, Bill's picture
Offline
Joined: 2011-09-30
Reputation: 0

David:
?
The "L" report only include the loads of the building, not the energy to run the HVAC system/central plant. The BEPS report includes the energy that the meters see.
?
John Aulbach