Dear all,

I would like to double check with you if I'm modeling my toilet exhaust
correctly, in order to answer the USGBC's design review comments
properly!

* The project has exhaust fans on the roof, with ducts to each
toilet (i.e., ducted exhaust).

* Since the toilets are not conditioned, I'm placing them
arbitrarily under random AHUs.

* I am then entering the exhaust flow rate and the kW per flow as
in the attached screenshot.

1. Can someone please confirm that the above is correct?

2. I assume ASHRAE 90.1 App G3.1.2.9 (baseline fan power
corrections) applies for toilet exhausts. I think I'll have to use the
correction factors for the

"Fully ducted return and/or exhaust air systems" (125 Pa). I'll
plug in the resultant kW/cfm in the input box in the attached drawing.
Correct?

Many thanks,

Omar

___________________________

Omar Katanani

Omar Katanani's picture
Offline
Joined: 2011-09-30
Reputation: 0

Omar - where is the air coming from that makes up the exhaust?

This affects how I would model toilet exhaust.

Aaron Dahlstrom , PE, LEED? AP

Dahlstrom, Aaron2's picture
Joined: 2011-09-30
Reputation: 4

Aaron,

It's most probably coming through infiltration (toilet door grills).

Best,
Omar
_____________________________

Omar Katanani

Omar Katanani's picture
Offline
Joined: 2011-09-30
Reputation: 0

Omar -

Pulling this back on list to close the loop ...

If you have toilet exhaust pulling makeup from adjacent zones, I see two options for the proposed case:

1) The standalone approach: Double-check that you have adequate fresh air supplied in the design and in the model to make up the fresh air being exhausted. Specify the exhaust fan as a direct meter load and give it the correct kW and operating schedule to match the design intent. Assume the makeup air operates properly.

2) The explicit approach: create the exhaust fan as an exhaust fan in the zone where the makeup air is coming from. In your proposed case, specify the kW/cfm and operating schedule to match the fan's intended design / operation. Since eQUEST will not allow transfer air across zone boundaries, this placement ensures that the makeup air comes from the correct location.

In either case, I don't believe the reviewer will allow an additional allowance in the baseline for Exhaust Fan motor horsepower beyond that specified by G3.1.2.9. Note that G3.1.2.9 gives a single cap for supply, return, exhaust and relief fans, which I have interpreted in the past to mean that all fans associated with a given quantity of supply air must trade under the same cap. So no separate allowance for the exhaust fan beyond what you have already allowed for the system supply fan that is supplying the fresh air to this area. (This is consistent with the definition of fan system bhp from the definitions section of ASHRAE 90.1). So - you can either: 1) zero out your exhaust fans in your baseline and allocate all of the allowance to the main system supply fan or 2) allocate some of the G3.1.2.9 allowance to the exhaust fan, perhaps based on the ratio of brake HP of the exhaust fans to the supply fan in the design case. The nature of your scheduling and whether the central system is CAV or VAV may recommend one approach or the other.

Hope this helps.

Aaron Dahlstrom , PE, LEED(r) AP

Dahlstrom, Aaron2's picture
Joined: 2011-09-30
Reputation: 4