Hello everyone,

User's manual for ASHRAE 90.1 says "For systems 1,5 and 7 (except for
purchased hot water or steam), the baseline building design hot water pump
power shall be 19 W/gpm". (page G-30)

I am confused if I have to use the proposed pumps in case I have purchased
hot water.

The chilled water pumps are always (as i understand) modeled at 22 W/gpm.

--

Thanks and Best Regards,

Sincerely,

Varun Kulkarni , M.S. , EIT

varun kulkarni's picture
Offline
Joined: 2011-09-30
Reputation: 1

Varun---

If you have purchased hot water in the proposed building and the project
is pursuing LEED certification (which I assume it is) you need to use
USGBC's Treatment of District or Campus Thermal Energy in LEED V2 and
LEED 2009 - Design & Construction. I've attached it as a reference.
You basically have two options: 1.) building stand-alone scenario where
only the downstream equipment is modeled and hot water is
metered/purchased, or; 2.) aggregate building/DES scenario where the
upstream equipment with its efficiencies or lack thereof are modeled in
the proposed design against 90.1.

Regards,

Andrew Craig PE, LEED AP

Andrew Craig2's picture
Offline
Joined: 2011-10-02
Reputation: 0

Thanks Andrew,

I did read this and we are according to this i have to change my system type
to 7 from system 5 as I have district heating and cooling.
But I am worried about the hot water pump W/gpm specifically.
Should I just or Can I just go ahead and use 19 W/gpm.