Adjusting Capacity for Unmet Cooling

13 posts / 0 new
Last post

Hello All,

I would like to know how other increase their baseline capacity when they have
unmet load. I have a PSZHP system?and in one system, I got more than?400 hrs
unmet load. I usually just increase the TR cooling capacity until?I get a lower
unmet load but in this case, I think?the unmet load is due to low supply cfm. Is
it ok to adjust also the supply fan cfm??I am thinking that G3.1.2.2 only
requires?me to adjust?only the cooling capacity. Do others adjust?both cfm and
cooling load?

Thanks,

Jaigath

Jaigath Chandraprakash's picture
Joined: 2011-10-02
Reputation: 0

An HTML attachment was scrubbed...
URL:

Nearedge's picture
Offline
Joined: 2011-09-30
Reputation: 0

Neeraj, it is in fact the contrary.

ASHRAE 90.1-2007 Appendix G requires you to model Baseline Airflow Rate using a 20-degree F temperature difference between the supply air and room air temperatures. Therefore, if your room set point is 75F for cooling, set your cooling leaving air temperature to 55F and vice versa for heating; 72F heating set point requires a 92F leaving air temperature. This establishes your CFM airflow within the model. Do not vary these to adjust unmet hours.

If you have unmet heating or cooling hours (over 300 or greater than 50 between baseline and proposed), you may incrementally adjust the baseline cooling and heating capacities (originally oversized 15% and 25% respectively) accordingly to reduce the overall unmet hours (below 300) or the difference between baseline and proposed (within 50).

Before taking this step, be sure to look at your thermostat drift points. If the cooling set point is 75, but the cooling drift point is 84, when the space is unoccupied this would allow the space to move toward 84 degrees. When the space becomes occupied and the simulation tries to cool to 75, the system will not be able to achieve this within the allotted time (1 hour) and you will have an unmet cooling hour.

There are some changes to ASHRAE 90.1-2010 that will effect unmet hours, but for the time being, if you are modeling a project using 2007 or 2004, this method should help you eliminate the unmet hours.

Regards,

Michael M. Collarin, EIT, LEED AP BD+C

Michael Collarin's picture
Joined: 2011-10-01
Reputation: 0

Hi Michael,

I?d like to offer a quick heads up ? your interpretation of what 90.1 has to say regarding addressing unmet hours is spot on and well-stated, no disagreements here. Neeraj however is indirectly making a pretty valid point that I?d hate for anyone to miss?

If you only ever approach addressing unmet hours by bumping the oversizing factors, you may well be missing something critical. I for one was in this train of thought when I started out. To the letter of the standard, indeed this is all we?re *prescribed* to do to remedy the situation, but this approach will not always work, and may result in baseline models with a very skewed performance ? suffice it to say skewed is not always a *good* thing, even if it does make your performance numbers look good.

Whenever I have unmet hours, I?ve learned through others on these lists to investigate the ?why? and ?when? of those unmet hours as a first step. More often than not, unmet hours in my models, when they do occur, have nothing to do with lacking heating or cooling capacity ? fan (airflow) scheduling conflicts, thermostat setpoints and unrealistic deadbands are the primary culprits. The systems effectively aren?t running as frequently or for a duration as they should be.

When this is the case, and I can assure Neeraj is not alone in this experience, fluffing the oversizing factor may appear to ?remedy? the issue, but often as not may *not* be enough to pull your baseline/proposed models into the prescribed requirements for unmet hours. In some cases, you might even make the situation worse. I?m pretty sure the spirit of the standard, by specifying a maximum number of unmet hours, is to allow both the proposed and baseline systems to run when they need to satisfy the loads

For whatever combination of reasons, and luck may be a part of it, it has been a long while since I?ve created an autosizing 90.1 baseline model whose unmet hours did not ring in at either zero or the single digits, and as such did not require any adjustments. I personally feel this has had a lot to do with understanding the mechanics behind what defines and can cause an unmet hour ? as you?re getting at with consideration to drift points.

As you say, future versions of 90.1 may be more nuanced, but I personally feel the manner in which unmet hours are currently addressed does a disservice to those aspiring to be quality energy modelers ? one can easily be misled to believe an unmet load hour is a problem in and of itself with an easy ?fix,? without recognizing it?s really a symptom of a problem... bumping capacities without first addressing the cause of unmet hours is something like a doctor only giving you a band-aid for a cut when what you need is a tetanus shot!

It may be worth mentioning that my experience is dominantly within the world of eQuest/DOE2. I would not be surprised to find other engines/software have varying ?typical? causes of unmet hours.

Anyway, that?s my two cents, for what it?s worth =) ? hope it might help lead others along the path!

NICK CATON, E.I.T.

Nick-Caton's picture
Offline
Joined: 2011-09-30
Reputation: 805

Hi All,

I think Nick is spot on in his discussion re unmet hours. While I'm not
saying it's a wrong thing to do, I personally have never used oversizing the
system as a way to get rid of unmet hours.

As an example, I have been helping someone off the list with his project, a
seemingly very simple building with only 5 thermal zones and one PVAVS air
handler with dx cooling and hot water heating - system 5. After running my 4
exposures, and having none of them with *any* hours of unmet loads, I
calculated my kW/cfm, heating load, cooling load, boiler kW and all of that,
put the calculated results in the baseline, reran the baseline, and for some
darn reason I had over 1000 hours of unmet cooling loads.

I checked all my inputs, made a few changes, reran the 4 exposures, and not
much changed. So, I put on my thinking cap and read Nick's email - not
necessarily in that order. One of the things that occurred to me is that
since the building is turned off all weekend my Monday morning pull down
loads during the summer might be the cause of the problem, so I put in an
optimum start schedule (this might have been required, I haven't double
checked) and my unmet hours were reduced by about 300 hours. I had an
adequate cfm/sf, something I'm not shy about raising at all since eQUEST
defaults it to 0.5 cfm/sf which is usually too small, so I didn't change it.
Then I looked at the throttling-range.

For VAV systems the eQUEST/DOE2 manuals say that the throttling range should
be *at least* 4 degrees to insure stable operation and that is what I had it
at originally. After thinking about it and doing some simple math in my head
I raised it to 6 degrees. My cooling temperature is set at 75 degrees so
this means when my room temperature reads 79, set point temp + 1/2 TR + 1
degree, my cooling coils will be activated. Before I did this I had also
looked at my SS-F reports and could see that my room temps weren't that far
off from the set point temp when I had under cooled hours reported. Using
the new throttling range brought me down to less than 500 hours of unmet
loads, which may work.

So this is an example of the thinking around what's going on and developing
a strategy that makes sense for a specific building. I also looked at my
heating/cooling temp schedules, etc., as Nick mentioned. What baffles me is
why, after none of my 4 exposures showed any unmet load hours, my baseline
did. I, like Nick, have not had that happen before. Perhaps it has something
to do with the way the building was zoned, 4 exposures and a core but I
don't know for sure.

Any ideas?

Carol

cmg750's picture
Offline
Joined: 2010-10-05
Reputation: 0

Some good discussion about unmet hours, to summarize_

Check_
a. Occupied setpoint, unoccupied drifting point delta
b. Throttling range
c. Fan schedule conflicts with load req.

What about additional considerations like_
- Conflicting mix of zones supplied by AHU
- Extreme zone controlling thermostat
- Perimeter condition not addressed
- Water line sizing inadequate to meet flow
- Missing pumps

Arpan Bakshi

NYCCTgreen's picture
Offline
Joined: 2011-09-30
Reputation: 0

I deal with unmet hours by supplying more air rather than upsizing capacity,
and it has worked.

Jorge E. Torres Coto

Jorge Torres-Coto2's picture
Joined: 2011-10-02
Reputation: 0

Hi All,

Does anybody know a good converter from 3D dxf to gbXML ?
Hopefully shareware.
I want to use the gbXML as input to DesignBuilder.
Appreciate your help.
Regards,

Iulian David

iulian's picture
Offline
Joined: 2010-12-09
Reputation: 0

Nick,

Thank you for the response. My first energy modeling experience was with eQuest, but have been using Trane?s TRACE 700 more extensively. In addition to the bldg-sim lists, the TRACE support is an excellent resource for those using the software, especially when it comes to unmet hours.

As you mention, and as I was alluding to in my third paragraph (starting with ?Before taking this step,?), there are certainly other areas that should be addressed prior to adjusting the cooling and heating capacities. I was not trying to cover all of them and did not want to get too in depth, as there are numerous areas that could be contributing to the unmet load hours and a review of the model would be necessary to determine what changes must be made to remedy the model. I?d like to note that I said the model and not the unmet hours. As you and Carol have illustrated, I fully agree that we aren?t supposed to be trying to manipulate the model to give us our desired outcome, but rather provide an accurate model. I do not think anyone should be taking liberty with the capacities to such extremes just to meet the requirements for unmet load hours. I even scratched my head the first time I read through that section and thought, ?well what?s the point??

My response wasn?t meant to suggest that modelers wildly vary cooling and heating capacities to obtain their desired results, but to clarify that Neeraj?s comment (copied below) was in fact contrary to what ASHRAE requires in Appendix G. Perhaps a few disclaimers were in order J

Correct me if I am wrong but on the contrary I think that ASHARE baseline PRM fixes the cooling and heating capacities to 1.15 and 1.25 respectively and the user is allowed to bump up the supply CFM in increments if necessary.

In conclusion, I offer these bullet points:

? Design airflow rates are set using a 20-degree delta T between supply air and room space

o These shall not be adjusted to ?fix? unmet hours

? Baseline cooling and heating capacities are initially set to 115% and 125% respectively

o These may be adjusted incrementally, but should not be relied upon to ?fix? a poorly produced model. In fact, their adjustment should be considered last, after all other approaches have failed.

? It is important to understand what an unmet hour is and why they occur

o It is of even greater importance to remedy the cause of the unmet hour rather than ?fudging? the numbers

o Refer to your software?s Building Temperature Profile report, if such a report exists, to help find the source (space, system, etc) of the unmet hours

o Thermostat Drift Points and Utilization Schedules have been primary culprits

? Other areas affecting unmet hours include but are not limited to the following: Thermostat placement, fan cycle operation, optimum starts, building envelope entries, Ventilation (outside air) schedules

Happy modeling!

Michael M. Collarin, EIT, LEED AP BD+C

Michael Collarin's picture
Joined: 2011-10-01
Reputation: 0

Iulian

I'm not aware of any direct conversion possible from 3D dxf to gbXML. You
should be able to import a 3D dxf into SketchUp though which might give you
some options for exporting afterwards. Certainly with the IES you can
use a plugin to export the model back out.

Kind regards

Pete

Pete Murray2's picture
Offline
Joined: 2011-10-02
Reputation: 0

I can't give an exact answer, but the first thought is that DXF is for
geometrical information, while the gbXML schema is for thermal properties
and zoning, hence the DXF isn't generally directly converted or even
convertible into gbXML.

More common though is to import DXF into Sketchup and then use the geometry
as a basis to trace the thermal zoning. I have done this using a DXF in
OpenStudio (http://apps1.eere.energy.gov/buildings/energyplus/openstudio.cfm)
to create (manually) an IDF file, which is the input file for EnergyPlus.

You could check whether DesignBuilder can import IDF geometry (it is based
on EnergyPlus after all!), and there could be your solution, let me know how
it turns out!

Cheers and good luck,

Marcus Jones, LEED AP

Marcus's picture
Offline
Joined: 2011-10-02
Reputation: 0

Hi Iulian - our free BIM energy modeler, Vasari, can bring in .dxf files and process gbXML natively or export to both .inp & gbXML.

Autodesk Vasari Details
Price: Free
Download: http://labs.autodesk.com/utilities/vasari/
Download Time: 2 - 4 minutes
Exports: gbxml, .inp, idf, dwg, dxf, fbx, sat, dgn, rvt, pdf
Imports: dxf, dwg, dgn, .sat, .skp,
Kernel: Revit native format (rvt)

Autodesk Vasari Native Simulation
- DOE 2.2 Whole Building Simulation
- Incident Solar Radiation

Jerry Jackson

Jerry Jackson's picture
Offline
Joined: 2011-09-30
Reputation: 0

Julian,
We have been working in a pretty complicated (geometry wise) project and we have managed to export .gbxml files to be imported in Design Builder using AutoCAD MEP.
However, there was an issue in DB with the number of vertices in each node (if I remember correctly could not handle more than 3 vertices per node for a building block). We went around this problem by importing it as outline block then cutting it accordingly, then converting it to building block, then adding holes and finally merging the adjacent zones. Long process but eventually it worked. If your geometry is simpler it would not be that difficult.

Best regards,
Harris Poirazis

Harris Poirazis's picture
Offline
Joined: 2011-10-02
Reputation: 0