dear all,

while checking through my simulation reports, i have realized that the the
number of cooling unmet hours for one of my projects is 579 hours. this far
exceeds the tab of allowable 300 hours. can anybody please explain me the
idea behind cooling unmet hours.

any help is greatly appreciated.

thank you
--
Regards,
Ar. Kirti Pramod Pabrekar.

kirti pabrekar's picture
Offline
Joined: 2011-09-30
Reputation: 0

Hi Kirti,

essentially, the rooms that are asking for cooling energy are not getting it
for some reason...this is the reason (or input) that you need to find to be
the culprit of not providing enough energy or not letting the cooling energy
get to the spaces that are asking for cooling.

Start by going to the SS-R reports after you see the unmet hours in your
BEPS/BEPU reports. Find which zones/systems are the culprit of the issue.
Next go to the SS-F reports for each zone that is being undercooled and this
will help you determine what also might be happening.

Hope this is a start to getting you the info you are looking for.

Cheers,
Pasha