Your cooling and heating schedules will still have to be temperature schedules for a two-pipe system. To make your 2-pipe system switch from heating to cooling you want to go under your 2-pipe loop and specify a ?snap? temperature. This is found under the operations tab, ?loop operation?.
You can also create an ?on/off/temp? schedule under the availability schedules of your unit?s cooling and heating coils if there are additional periods when cooling or heating are not allowed for specific air handling units.
Your cooling and heating schedules will still have to be temperature schedules for a two-pipe system. To make your 2-pipe system switch from heating to cooling you want to go under your 2-pipe loop and specify a ?snap? temperature. This is found under the operations tab, ?loop operation?.
You can also create an ?on/off/temp? schedule under the availability schedules of your unit?s cooling and heating coils if there are additional periods when cooling or heating are not allowed for specific air handling units.
I hope this answers your question.