I need to model radiant ceiling for heating and cooling both. As per the suggestions in the archive (quoted below), I kept the system as VAV, reduced fan usage to represent radiant slab system's fan usage, kept my heating by water loop baseboards and cooling by DX and coil head and loop temperatures as per radiant slab system but after selecting the system type as 'VAV', in the cooling page, it won't allow me to select 'electric DX' as the cooling source.

Kindly advice how can I solve this problem.

Thanks a lot,

Shalini

[Equest-users] How do I model a building with radiant slab heat ANDair conditioning?

Bishop, Bill
wbishop at pathfinder-ea.com

Tue Mar 2 14:03:52 PST 2010
Previous message: [Equest-users] How do I model a building with radiant slab heat AND air conditioning?
Next message: [Equest-users] ASHRAE Baseline EUI
Messages sorted by:
[ date ]
[ thread ]
[ subject ]
[ author ]

Rob,

Select the system based on the DX air conditioning, then add hot water
baseboards for the radiant slab. Set your baseboard capacity, coil head,
loop temperature etc. to match the radiant slab heating system.

Regards,
Bill

William Bishop, EIT, LEED(r) AP

Shalini Modi's picture
Offline
Joined: 2011-09-30
Reputation: 0
rdh4176's picture
Offline
Joined: 2011-02-14
Reputation: 0
NYCCTgreen's picture
Offline
Joined: 2011-09-30
Reputation: 0

Thanks, Rob and Arpan. I will try using fan coil units - will that be a good representation of radiant slab heating and AC? As soon as I select VAV/PVAV as the system type, the cool source in the cooling tab doesn't allow any change...why is that so?

Shalini

Date: Mon, 25 Apr 2011 13:54:36 -0400
Subject: Re: [Equest-users] Radiant ceilings

Shalini Modi's picture
Offline
Joined: 2011-09-30
Reputation: 0

I would still use baseboards for radiant heating, FCU for radiant cooling.
Build secondary water-side loops and assign baseboards to heating hot water
secondary loop and fan coil to secondary chilled water loop.

NYCCTgreen's picture
Offline
Joined: 2011-09-30
Reputation: 0

Arpan,

Thanks a lot for your response. I totally see what you are saying. I can sure create a how water and a chilled water loop and select 'hot water loop' as my heating source in heating tab. But in my cooling tab, my model wouldn't allow me to select a 'cool source' at all! It sticks with n/a, even though the drop down menu shows chilled water and electric DX as options, it won't let me select any of them....what do I do and why is this so?

Your response will be greatly appreciated.

Date: Mon, 25 Apr 2011 14:19:51 -0400
Subject: Re: [Equest-users] Radiant ceilings

Shalini Modi's picture
Offline
Joined: 2011-09-30
Reputation: 0